Understanding Hospital Emergency Power Supply Systems

Generators and emergency power systems are essential to enabling hospitals and health care facilities to effectively serve their communities

Learning Objectives

  • Gain a basic understanding of the generators and major components of an emergency power system for hospitals.
  • Understand the regulatory requirements for an emergency power system for hospitals.
  • Provide an approach to the design of these systems that accounts for key client and project needs.

Due to constant changes in medical standards of care, technologies and building systems, hospitals have become more reliant on electrical systems to function properly. As such, the reliability of the hospital building’s electrical system is more important than ever.

NFPA 70: National Electrical Code requires every hospital to have two independent power sources that provide a minimum level of reliability: a normal source (i.e., utility) and an alternate source (i.e., generator, fuel cell system or battery system).

Because most health care facilities have traditionally used generators as their alternate source due to runtime and maintenance advantages, this article will focus on generators and essential electrical system (i.e., “emergency power”) design.

For the purposes of this article, the NEC Article 517 term “essential electrical system” and Article 700 term “emergency power system” are synonymous because emergency systems are defined in NEC Article 700, which is applied specifically to hospitals in NEC Article 517.

An emergency system is defined by the NEC as “those systems legally required and classed as emergency by municipal, state, federal and other codes.”

NFPA 110: Standard for Emergency and Standby Power Systems defines the various components that makeup an emergency power system and comprises the emergency power supply and emergency power supply systems.

The EPS is the alternate power source, which in this case is the generator(s). The EPSS consists of the conductors, distribution equipment, overcurrent protective devices, transfer switches and all control, supervisory and support equipment needed for the system to operate between the generator and the transfer switch. Conductors, distribution equipment and overcurrent protective devices on the load side of the transfer switches are not considered part of the EPSS per NFPA 110, but are considered part of the overall emergency power system (see Figure 1).

Figure 1

A generator consists of two major components: the engine that provides the mechanical power via a rotating drive shaft and an alternator, which converts the mechanical energy to electrical energy. A transfer switch is an electrical piece of equipment that is configured to connect two incoming power sources (typically the utility source and the generator source) and one outgoing connection to the load(s) using a switching mechanism to select which of the two incoming sources is connected to the load (see Figure 2).

Figure 2: Typical generator set configuration with major components identified (this example is an indoor installation).

There are other regulatory bodies, codes and organizations that need to be considered depending on where the project is located:

Reviewing the requirements of these regulatory bodies, codes and publications is recommended at the onset of a new project to determine any project specific impacts as the adopted codes vary by state and local jurisdictions.

Emergency power design considerations

Generators are manufactured with two ratings: prime and standby. A prime rated generator is designed to be operated continuously as the primary source of power for the system, typically used where utility power is not available such as extremely rural locations. A standby rated generator is designed to operate intermittently when the main source of power fails or during generator testing. Emergency power systems for hospitals use generators rated for standby use because the generator is functioning as the alternate source of power.

NFPA 110 requires generators and the EPSS to have a Classification, Type and Level. The “Class” defines the minimum run time in hours. The “Type” defines the maximum time, in seconds, to transfer to the alternate source after power loss. The “Level” defines the risk to human life due to the failure of the system.

Hospital emergency power systems typically must be Class 96 (minimum 96 hours of runtime) or have an operational plan to supply 96 hours of fuel to the site, Type 10 (maximum 10 seconds to transfer) and Level 1 (failure of system could result in loss of human life or serious injuries).

The two common fuel types for hospital generators are No. 2 diesel and natural gas. Typically, hospitals opt to install diesel generators for two primary reasons.

  • Hospitals are required to either have 96 hours of fuel stored on-site or an agreement to have the additional fuel delivered to maintain 96 hours of continuous runtime (see the Joint Commission’s Emergency Management 96 Hour Plan for details). Natural gas is delivered to the hospital from the utility via underground distribution piping and cannot be stored on-site in the quantities required. Authorities having jurisdiction do not typically consider an off-site fuel source reliable enough to be the sole fuel source for generators (see NEC 700.12(D)(2)).
  • Emergency generators and the EPSS for hospitals are required to be NFPA 110 Type 10 systems. This requires the system to restore power to the loads in less than 10 seconds. Most natural gas generators are not able to meet this requirement due to the time it takes the generator engine to start.

Generators can be installed indoors or outdoors. Indoor installations have the advantage of being better protected from weather and vehicular traffic and provide ease of maintenance but are typically a higher first cost. The generator room needs to be designed to account for the substantial airflow required to both cool the generators and provide combustion air to the generator. Ideally the air intake is at the back of the room and air discharge is at the front to promote proper airflow over the engine block to facilitate engine cooling. Rooms with air intake or discharge from above or one side of the room may create cooling issues and should be avoided. Design also needs to consider the acoustical impact of the generators at both the air intake and discharge locations. Generators create a lot of noise and sound attenuation within the room may be required to meet local ordinances or hospital requirements (see Figure 3).

Figure 3: Example of an indoor (left) and outdoor (right) generator installation

Outdoor installations typically have a lower first cost but are not as accessible and may be susceptible to degradation of the equipment over time if not properly protected. Typically, a generator installed outdoors will have a weather-proof enclosure with dampers and heating elements to keep the environment within the enclosure controlled to an extent. The enclosure also may have a sub-base tank for fuel storage, sound attenuation or raised personnel platforms depending on the specific requirements of the project. The self-contained nature of an outdoor generator can be advantageous as the issues with ventilation and fuel oil delivery are simplified.

Emergency power distribution equipment

The complete essential electrical system, as defined by NEC Article 517, consists of the EPSS (i.e., everything between the transfer switch and the generator, including the transfer switch) and the switchboards, panels, transformers, feeders and overcurrent protective devices that are connected to the load side of the transfer switch.

In hospitals, the essential electrical system is divided into three separate branches per NEC Article 517: life safety, critical and equipment. Each branch has its own automatic transfer switch, or switches depending on the size of the system, to segregate power distribution in the hospital:

  • The life safety branch is limited to circuits essential to life safety and include illumination of means of egress, exit signs, select alarm and alerting systems, communication systems, generator set accessories, elevators and select automatic doors.
  • The critical branch is primary reserved for systems and equipment that are essential to patient care and safety and include, but is not limited to, task illumination and receptacles patient care spaces, nurse call systems, clinical information technology systems and select power circuits needed for effective hospital operation.
  • The equipment branch primarily consists of mechanical equipment required for effective hospital operation and typically includes air handling units, pumps, boilers, chillers, medical vacuum/compressed air equipment, kitchen equipment and any other optional loads the hospital considers necessary to maintain the facility when utility power is lost.

Transfer switches can be either automatic, nonautomatic or manual. Hospitals primarily use automatic transfer switches, which transfers to generator without personnel input. However, nonautomatic and manual transfer switches are used for optional loads when automatic transfer is not required or desired due to available generator capacity.

The difference between nonautomatic and manual is nonautomatic has an automatic transfer mechanism, but transfer requires personnel to initiate; manual requires personnel to physically move a mechanism by hand from one source to the other.

Automatic transfer switches have three transition types. Open transition is the most common in hospitals and disconnects from the primary source of power (utility) before connecting to the alternate source (generator), also known as “break before make.” Delayed transition is similar to open transition but has a built-in time delay where it is disconnected from both sources for an extended period and is most commonly used for mechanical equipment to allow time for motors to slow down before connecting to another source of power.

Closed transition is less common due to utility company approval needed before installation because closed transition briefly parallels utility with the generator(s). Closed transition will briefly connect to both sources before disconnecting from one source or “make before break.” The advantage is the facility does not experience a brief “blip” in power during monthly generator tests or when transferring from generator back to utility power.

Pictured: 3-Way Manual Transfer Switch includes three breakers which allow the permanent generator to be simultaneously connected to both a load bank (permanent generator testing) and the ATS

Many hospitals require automatic transfer switches to have bypass isolation. Bypass isolation is a switch provided with two switching mechanisms configured so that one switch can be removed and worked on in a safe manner while the other switching mechanism provides power to the loads. The design needs to consider the increased footprint and cost for bypass isolation switches over transfer switches with a single switching mechanism.

Common emergency power system configurations

There are two common system configurations that most hospitals use: standalone and paralleled systems. A standalone system consists of a single generator with transfer switches separating life safety, critical and equipment branch loads. The generator starts when a start signal is received from any of the transfer switches and each transfer switch will transfer to generator power once the switch senses the generator source has reached system voltage and frequency.

The advantage of a standalone system is typically lower first cost in comparison to a similarly sized multi-generator configuration as well as less complicated controls. The disadvantage is failure of the singular generator results in the facility having no backup power to essential loads during the utility outage. In addition, the standalone system has no ability to shed less critical loads if the generator is unable to keep up with the demand load of the facility during the utility outage unless a building automation system interface is provided to monitor real-time load on the generator and shutdown select equipment when it senses the generator is reaching peak capacity. This additional feature will add cost to the project if implemented, which needs to be considered during design.

A paralleled configuration consists of two or more generators connected in parallel to a common bus with multiple transfer switches. Once a start signal is sent by a transfer switch, the first generator to reach rated voltage and frequency will close to the bus. Transfer switches will start transferring to the generator source and subsequent generators will close to the common bus once they reach voltage/frequency and are synchronized with the first generator.

The advantage of paralleled configuration is it provides equipment redundancy in the event a generator fails to start or is offline for repairs. Additionally, the system is able to load shed lower priority transfer switches (i.e., disconnect them from the generator source) if the generators are unable to keep up with the demand load. This prevents a complete outage to the facility and ensures the most critical loads remain operational.

Electrical system redundancy

Hospitals are constantly preparing for the worst-case scenario to ensure they deliver the highest level of care to their patients. Equipment and system redundancy is a priority. It is recommended that designers discuss equipment and system configurations that provide inherent redundancy with the client to ensure the design meets the client’s redundancy requirements and project budget.

For generators, a common configuration is to provide the quantity of generators that provide N+1 redundancy in the event one of the generators fails to start or is offline for repair. For example, if a facility has a peak demand load of 900 kilowatts and the hospital wants N+1 redundancy, providing three 500-kilowatt generators in a paralleled configuration would meet the redundancy goal.

Another strategy to improve the resiliency of the essential electrical system is to separate critical or equipment branches of emergency power into “Critical A” and “Critical B,” each having its own automatic transfer switch. This limits the potential outage to the facility due to a catastrophic failure to a transfer switch or other distribution equipment on that branch of power. It also allows for critical care areas of the hospital to be connected entirely to emergency power while maintaining two separate sources of power which is required by code.

Generator fuel

As previously noted, No. 2 fuel oil is the most common fuel source for hospital emergency generators. Typically, a hospital will have a minimum of 96 hours of fuel on-site, and may have less if complying with the Joint Commission’s Emergency Management 96 Hour Plan or in a local jurisdiction that has a less stringent requirement.

Depending on the utility’s reliability, the generators may only run 15 to 20 hours a year to meet the monthly/yearly testing requirements for each generator. This results in fuel that may sit for extended periods before being used. To avoid degradation of the quality of fuel, most hospitals will install a fuel polishing system to remove water and other particulates from the fuel oil. If a centralized tank is installed to serve multiple generators, a fuel oil pumping system will supply and return fuel to the generator day tanks that are located at each generator.

Modifications, upgrades to existing electrical systems

When designing a generator or emergency power system upgrade for an existing hospital, phasing and outages need to be considered at the outset of the design as they can have a huge impact on hospital operations. Hospitals cannot afford to shut down critical services at any time.

Although outages are unavoidable with a major system upgrade, discussions with hospital administration and key personnel early in the design is crucial as it may require a different design approach to meet the project goals and maintain the facility during construction.

Generators and emergency power systems are an essential system in hospitals to ensure the operational impact of a utility outage is minimal. As health care facilities and staff continue to adapt to the latest standards of care, the need for more robust and reliable emergency power systems will be required.

When initiating the design of a new emergency power system or upgrade to an existing system, owners and design professionals need to be in constant communication to ensure the design aligns with the project goals, budget and hospital’s operational priorities.

Emergency generators and the design of power systems play a crucial role in ensuring reliable power is provided at each facility by providing an alternate source of power in the event the utility source is interrupted.

View the original article and related content on Consulting Specifying Engineer

ESL Power Systems, Inc. Partners with France Based Company PROCONECT

CORONA, California, July 2022 – ESL Power Systems, Inc. is pleased to announce an exclusive distribution agreement with PROCONECT, a French manufacturer specializing in industrial connectors. This partnership will allow ESL to utilize and distribute PROCONECT’s premier low and medium voltage push-pull receptacles and plugs; harnessing the expertise from both companies and providing advanced Shore Power Solutions for Cruise, Ferry, Ports and Container Terminals across all Americas.

Together, ESL and PROCONECT will offer safe, proven technology that is reliable, durable, and heavy duty for marine grade applications; in addition to offering compliance with local electrical regulations and codes.

This agreement grants ESL exclusive distribution in the Americas of PROCONECTs products for marine applications such as electrification of container handling equipment (ERTGs, RMGs, STS), and shore power for containers, ferries, cruise terminals and other types of vessels. ESL’s expertise and footprint in the market will offer PROCONECT customers local stock, support, and technical assistance.

PROCONECT CEO, Béatrice Barokhel states, “We are excited to be working with ESL and expanding PROCONECT’s reach for the port and maritime industry to the Americas. ESL’s custom solutions, excellence in customer service and dedication to innovation fall in line with PROCONECTS mission to serve our customers in a market that demands performance, timely delivery, and cost value.”

ESL President, Marcelo Gonzalez shares PROCONECT’s excitement. “We couldn’t be happier to work with a European company that supplies such a quality product to the port and shore power markets. We at ESL believe this partnership will provide our customers with the absolute best in quality connection for marine environments.”

For additional information or a project quote contact ESL’s Sales Team at: info@eslpwr.com

About ESL Power Systems, Inc.
A 100% employee-owned company located in Corona, CA, ESL Power Systems, Inc. is an innovative global leader in the design and manufacturing of cord-connected electrical equipment for industrial and commercial applications and is known as best-in-class builders of Ship-to-Shore Power Equipment. ESL works with customers globally to build custom engineered solutions for commercial and military applications such as: Cruise Lines, Ferry Terminals, Navy/NATO Ships & Bases, USCG Ships & Bases, and Container Ships & Ports Barges.

About PROCONECT
Created in 1981, PROCONECT is a French company located in Orvault, France that specializes in the conception of industrial connectors. Thanks to its high interest for Research and Innovation, PROCONECT is a very dynamic, creative and speed reactive company serving a market with high demand in performance, cost, and delivery time. ISO 9001 certified since 1998, PROCONECT is also registered as a NATO supplier.

Download ESL’s Enclosure Type Presentation

Download ESL’s Enclosure Type Presentation

ESL’s Enclosure Type presentation is now available for download! This deck includes all you need to know in an easy to reference slide format for various enclosure type ID’s, NEMA and UL requirements and the intended application for each enclosure.

How Can We Help?
If you have any questions or require a project quote, ESL is here to help. In addition to our world-class customer service team, we aim to provide each customer with a knowledgeable network of Manufacture’s Representative Agencies to provide timely service when you need it the most. Just click the button below to contact us!

ESL President cuts ribbon to new facility

ESL Makes Big Moves: Fabrication Building Ribbon Cutting Event

In November of 2020 ESL made moves for the future and leased a building 1,000 feet away from its headquarters at 2900 Palisades Dr. This new facility doubles ESL’s fabrication capacity and provides a clear path for continued growth and prosperity for ESL Employee Owners. The official Ribbon Cutting ceremony for ESL’s Fabrication Building Expansion took place this month with Mayor, Jacque Casillas and Council Member Jim Steiner in attendance along with the ESL Leadership team. ESL President Marcelo Gonzalez and Chief Sales Strategists Michael Hellmers spoke to the group about ESL’s bright future. They emphasized how this expansion gives ESL the ability to improve processes and lead times making it possible for our organization to fulfill commitments to our customers and accomplish our Mission of making it easy to do business with ESL.

ESL Announces the Launch of Its Newly Redesigned Website

ESL Announces the Launch of Its Newly Redesigned Website

CORONA, California, October 29, 2020 – ESL Power Systems, Inc., a global leader in providing safety-interlocked power solutions for cord-connected electrical equipment is proud to announce the launch of its newly redesigned website at eslpwr.com. The new ESL website includes redesigned architecture focused on customer ease of use while navigating ESL’s extensive range of product offerings.

Created with the user experience in mind, ESL’s new website includes many updated features to help users quickly and easily navigate the site.

Showcase navigation allows users to easily navigate to any product offering from any page resulting in decreased clicks for site browsing.

Enhanced site search with quick view. Easily search across the entire site for catalog sheets, product specifications or blog posts by entering key words. Hover over search results to see thumbnails of each page.

Ask a Question and Quote Requests buttons readily available. ESL’s knowledgeable customer service team is here to help you determine what solution is best for your project. In addition to our online request forms, you can give us a call by tapping our number at the top of any page from your handheld device. Our goal is to easily connect you to one of our exceptional customer service members for project direction in the medium that’s best suited to you.

Determine where to buy our products across the U.S. Visit our new Local Rep Map and find a manufacturer representative group near you.

ESL has also made our helpful videos more accessible including highlights on recently published videos directly on the navigation menu.

“The ESL website is the foundation of our online presence. As our organization focuses on strategic growth, our site functions as a critical tool to establish brand recognition all while making our customers experience a better one,” stated ESL President Marcelo Gonzalez.

ESL is proud of the new website which complements our brand, vision and showcases our company in a way that is reflective of the quality of service and product supplied to our customers. Check it out now!

Media Contact:
Erika Thorson
ESL Power Systems, Inc.
2800 Palisades Dr.
Corona, CA 92878
+1 (951) 739-7000
ethorson@eslpwr.com
https://eslpwr.com